3 - 14 
MELSEC-A
3   SPECIFICATIONS AND FUNCTIONS 
 
3.4  Specifications of input/output signals for master module 
3.4.1 List of input/output signals 
The D75P2 uses 128 input points and 128 output points for exchanging data with the 
master module. 
The input/output signal assignment and signal names are shown below. 
Device RX refers to the signals input from the D75P2 to the master module, and 
device RY refers to the signals output from the master module to the D75P2. 
 
Signal direction: D75P2   master module 
Signal direction: Master module   D75P2 
Device No. 
Signal name 
Device No. 
Signal name 
RXn0 D75P2 
READY 
RYn0 to 
RYnF 
Use prohibited 
RXn1 
Axis 1 start complete 
RXn2 
Axis 2 start complete 
RXn3 Use 
prohibited 
RXn4 
Axis 1 BUSY 
RXn5 
Axis 2 BUSY 
RXn6 Use 
prohibited 
RXn7 
Axis 1 positioning complete 
RXn8 
Axis 2 positioning complete 
RXn9 Use 
prohibited 
RXnA 
Axis 1 error detection 
RXnB 
Axis 2 error detection 
RXnC Use 
prohibited 
RXnD 
Axis 1 M code ON 
RXnE 
Axis 2 M code ON 
RXnF Use 
prohibited 
RX(n+1)0  Axis 1 speed limiting flag 
RY(n+1)0  Axis 1 positioning start 
RX(n+1)1  Axis 1 speed change processing flag 
RY(n+1)1  Axis 2 positioning start 
RX(n+1)2  Axis 1 drive unit READY 
RY(n+1)2  Use prohibited 
RX(n+1)3  Axis 1 zero point signal 
RY(n+1)3  Axis 1 stop 
RX(n+1)4  Axis 1 in-position signal 
RY(n+1)4  Axis 2 stop 
RX(n+1)5  Axis 1 near-point dog signal 
RY(n+1)5  Use prohibited 
RX(n+1)6  Axis 1 stop signal 
RY(n+1)6  Axis 1 forward run JOG start 
RX(n+1)7  Axis 1 upper limit 
RY(n+1)7  Axis 1 reverse run JOG start 
RX(n+1)8  Axis 1 lower limit 
RY(n+1)8  Axis 2 forward run JOG start 
RX(n+1)9  Axis 1 external start signal 
RY(n+1)9  Axis 2 reverse run JOG start 
RX(n+1)A 
Axis 1 speed/position changeover 
signal 
RY(n+1)A 
to 
RY(n+1)F 
Use prohibited 
RX(n+1)B  Axis 1 deviation counter clear status 
RX(n+1)C  Axis 1 speed controlling flag 
RX(n+1)D 
Axis 1 speed/position changeover latch 
flag 
RX(n+1)E  Axis 1 command in-position signal 
RX(n+1)F  Axis 1 zero point return request flag 
 
n: Address assigned to the master module by station number setting