To prevent damage, care must be taken not to apply too much torque 
when attaching gas supply pipe to gas valve inlet. 
Apply joint compounds (pipe dope) sparingly and only to the male 
threads of pipe joints. Do not apply compound to the first two threads. 
Use  compounds  resistant  to  the  action  of  liquefied  petroleum 
gases.
DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUTOFF 
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY 
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45Kpa). GAS 
SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM 
THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45Kpa) OR 
LESS, THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST 
BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING 
THE MANUAL GAS SHUTOFF VALVE.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR 
GAS LEAKAGE. USE SOAP AND WATER SOLUTION OR OTHER 
MATERIAL ACCEPTABLE FOR THE PURPOSE OF  LOCATING 
GAS LEAKS. DO NOT USE MATCHES, CANDLES, FLAME OR 
OTHER SOURCES OF IGNITION FOR THIS PURPOSE.
PURGING
Gas line purging is required with new piping or systems in which 
air has entered.
 
CAUTION
PURGING  SHOULD  BE  PERFORMED  BY  PERSONS 
EXPERIENCED  IN THIS TYPE  OF  GAS  SERVICE. TO AVOID 
RISK  OF  FIRE  OR  EXPLOSION,  PURGE  DISCHARGE  MUST 
NOT ENTER CONFINED AREAS OR SPACES WHERE IGNITION 
CAN  OCCUR. THE AREA  MUST  BE  WELL  VENTILATED AND 
ALL  SOURCES  OF  IGNITION  MUST  BE  INACTIVATED  OR 
REMOVED. 
GAS METER SIZE - CITY GASES ONLY
Be sure that the gas meter has sufficient capacity to supply the full 
rated gas input of the water heater as well as the requirements of 
all other gas fired equipment supplied by the meter. If the gas meter 
is too small, ask the gas company to install a larger meter having 
adequate capacity.
GAS VALVES
 WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE 
TO THE APPLIANCE.
SYSTEM CONNECTIONS
The system installation must conform to these instructions and to 
the local code authority having jurisdiction. Good practice requires 
that all heavy piping be supported.
THERMOMETERS (Not Supplied)
Thermometers should be obtained and field installed as shown in 
the installation diagrams.
Thermometers are installed in the system as a means of detecting 
the temperature of the outlet water supply.
RELIEF VALVE
This heater is equipped with an approved temperature and pressure 
relief valve. ASME ratings cover pressure relief. CSA ratings cover 
release rate with temperature actuation.
FOR SAFE OPERATION OF THE WATER HEATER, THE RELIEF 
VALVE(S) MUST NOT BE REMOVED OR PLUGGED.
In addition to the appliance relief valve, each remote storage tank 
which may be used in conjunction with this appliance shall also be 
installed  with  a  properly  sized,  rated  and  approved  temperature 
(ANSI) and pressure (ASME) relief valve(s). This relief valve shall 
comply with the standard for relief valves and automatic gas shutoff 
devices for hot water supply systems. ANSI Z21.22-CSA 4.4.
Your  local  code  authority  may  have  other  specific  relief  valve 
requirements.
  WARNING
THE PURPOSE OF A RELIEF VALVE IS TO AVOID EXCESSIVE 
PRESSURE  OR  TEMPERATURE  INTO  THE  STEAM  RANGE, 
WHICH MAY CAUSE SCALDING AT FIXTURES, TANK EXPLOSION, 
SYSTEM OR HEATER DAMAGE. NO VALVE IS TO BE PLACED 
BETWEEN THE RELIEF VALVE AND THE TANK.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE 
TO  DIRECT  DISCHARGE  TO A  SAFE  LOCATION  TO AVOID 
SCALDING  OR  WATER  DAMAGE. THIS  LINE  MUST  NOT  BE 
REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST 
NOT CONTAIN VALVES OR RESTRICTIONS, NOR SHOULD IT BE 
LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP THE 
END OF THIS LINE. RESTRICTED OR BLOCKED  DISCHARGE 
WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE. 
THE  DISCHARGE  LINE  SHALL  BE  INSTALLED  TO ALLOW 
COMPLETE DRAINAGE OF BOTH THE VALVE AND LINE.
WATER LINE CONNECTIONS 
This  manual  provides  detailed  installation  diagrams  (see  back 
section  of  this  manual)  for  typical  methods  of  application  for  the 
water heaters. 
The water heater may be installed by itself, or with a separate storage 
tank. When used with a separate storage tank, the circulation may be 
either by gravity or by means of circulating pump. When a circulating 
pump is used, it is important to note that the flow rate should be slow 
so that there will be a minimum of turbulence inside the heater.
CLOSED SYSTEM
 CAUTION
A closed system will exist if a check valve (without bypass), pressure 
reducing valve (without bypass), or a water meter (without bypass) is 
installed in the cold water line between the water heater and street 
main (or well). 
Excessive pressure may develop causing premature tank failure or 
intermittent relief valve operation. This type of failure is not covered 
by the limited warranty. An expansion tank or a similar device may 
be required in the inlet supply line between the appliance and the 
meter or valve to compensate for the thermal expansion of water 
under supply pressure.
If a water heater is installed in a closed water system, check local