POWERED ANODE SYSTEM
To insure a long, trouble-free operating life, SUF 300 and 400 
are factory equipped with a powered anode system.  The anodes 
are  of  a  permanent  design  and  do  not  need  replacing  unless 
damaged.
DRAIN VALVE AND ACCESS PANELS
The heaters are equipped with a 3/4" drain valve.
An access panel covers the cleanout opening in the tank which is 
sealed by a gasket and cover, see Figure 24.
RELIEF VALVE
At least twice a year, the temperature and pressure relief valve should 
be checked to ensure that it is in operating condition.  To check the 
relief valve, lift the lever at the end of the valve several times.  The 
valve should seat properly and operate freely.
If  water  does  not  flow,  remove  and  inspect  for  obstructions  or 
corrosion.  Replace  with  a  new  valve  of  the  recommended  size 
as  necessary.  Inspection  of  the  valve  should  be  performed  at 
least every three years. Do not attempt to repair the valve, as this 
could result in improper operation and a tank explosion. In areas 
with  poor  water  conditions,  it  may  be  necessary  to  inspect  the  
T&P valve more often than every three  years.
 CAUTION
BEFORE  MANUALLY  OPERATING  THE  VALVE,  MAKE  SURE 
THAT  A  DRAIN  LINE  HAS  BEEN  ATTACHED  TO  THE  VALVE 
TO DIRECT THE DISCHARGE TO AN OPEN DRAIN.  FAILURE 
TO TAKE THIS PRECAUTION COULD MEAN CONTACT WITH 
EXTREMELY HOT WATER PASSING OUT THE VALVE DURING 
THIS CHECKING OPERATION.
If the temperature and pressure relief valve on the heater discharges 
periodically or continuously, it may be due to thermal expansion of 
water in a closed water supply system, or, it may be due to a faulty 
relief valve.
Thermal expansion is the normal response of water when it is heated.  
In a closed system, thermal expansion will cause the system pressure 
to build until the relief valve actuation pressure is equaled.  Then, 
the relief valve will open, allowing some water to escape, slightly 
lowering the pressure.
Contact your water supplier or local plumbing inspector on how to 
control this situation.
Two  common  corrections  are  listed  in  the  Checklist  and  Service 
Information which appears later in this manual.
ABOVE ALL, DO NOT PLUG THE TEMPERATURE AND PRESSURE 
RELIEF VALVE.  THIS IS NOT A SOLUTION AND CAN CREATE A 
HAZARDOUS SITUATION.
VENT SYSTEM
Examine the vent system every 3 months. Points of inspection are 
as follows:
1.  Check for obstructions and/or deterioration of vent piping and 
vent hood. Replace immediately where needed.
2.  Vent pipe and vent hood screen should be cleaned of foreign 
material and soot. The screen is located inside the vent hood 
outlet and is accessible from the outside of the hood. Do not 
reach inside the vent hood when the heater is in operation.
3.  Check all vent system connections for leakage and reseal as 
required using Hi Temp Silicone sealer or equivalent.