Справочник Пользователя для Toshiba RAV-SP1404AT8ZG-TR

Скачать
Страница из 143
– 81 –
Red
White
Black
Connector : White
Red
White
Black
Table  Inspection of outdoor unit main parts
No.
1
2
3
Parts name
Compressor
(Model : DA422A3F-27M)
Outdoor fan motor
(Model : ICF-280-A100-1)
4-way valve coil
(Cooling/heating switching)
(Model : STF-01AJ502E1)
Checking procedure
Measure the resistance value of each winding by using the tester.
Position
Red – White
White – Black
Black – Red
Resistance value
0.79 ± 0.04 Ω
Under 20°C
Measure the resistance value of each winding by using the tester.
Position
Red – White
White – Black
Black – Red
Resistance value
14.8 ± 1.5 Ω
Under 20°C
Measure the resistance value of each winding by using the tester.
Resistance value
1435 ± 144 Ω
Under 20°C