Справочник Пользователя для Toshiba RAV-SM1100UT-E

Скачать
Страница из 80
28
Accessory parts and Parts to be procured locally
 Accessory parts
 Parts to be procured locally
Connecting pipe (Liquid side)
(6.35mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)
RAV-SM560UT-E, RAV-SM560AT-E
(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
RAV-SM800UT-E, RAV-SM800AT-E
RAV-SM1100UT-E, RAV-SM1100AT-E
RAV-SM1400UT-E, RAV-SM1400AT-E
Connecting pipe (Gas side)
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)
RAV-SM560UT-E, RAV-SM560AT-E
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)
RAV-SM800UT-E, RAV-SM800AT-E
RAV-SM1100UT-E, RAV-SM1100AT-E
RAV-SM1400UT-E, RAV-SM1400AT-E
Power supply cord
2.5mm² (H07RN-F or 245IEC66) or 3.5mm² (AWG-12)
Connecting cable (indoor and outdoor cable)
H07RN-F or 245IEC66 (1.5mm² or more)
Thermal insulation for refrigerant pipe
(10mm or more, thermal insulating foam polyethylene)
Thermal insulation for drain pipe
(10mm or more, foam polyethylene)
Drain pipe (Outer 26mm (diam.))
Tapes
Grounding cable (2.0mm (diam.) or more)
Part name
Installation
Manual
Heat insulating
pipe
Installation
pattern
Installation
gauge
Pattern fixing
screw
Heat insulator
Q’ty
1
2
1
2
4
1
Shape
This
manual
——
M5 x 16L
Usage
(Be sure to hand over to customers)
For heat insulation of pipe
connecting section
For confirmation of ceiling opening
and main unit position
For positioning of ceiling position
(united with installation pattern)
For attach the installation pattern
For heat insulation of drain
connecting section
Part name
Washer
Hose band
Flexible hose
Heat insulator
Owner’s
Manual
Q’ty
8
1
1
1
1
Shape
Usage
For hanging-down unit
For connecting drain pipe
For adjusting core-out of drain
pipe
For sealing of wire connecting port
(Be sure to hand over to customers)
<Separate sold parts>
Part name
Standard wired
remote controller
Q’ty
1
Shape
Usage
Model
RBC-AMT21E
Part name
Ceiling panel
Q’ty
1
Shape
Usage
Model
RBC-U21PG (W)-E
R
A
V
-SM1100A
T
-E
R
A
V
-SM1400A
T
-E