Справочник Пользователя для Goodman Mfg CE COMMERCIAL SPLIT SYSTEM AIR CONDITIONER

Скачать
Страница из 8
P
RODUCT
 S
PECIFICATIONS
SS-CE120
 www.goodmanmfg.com 
3
S
PECIFICATIONS
P
ERFORMANCE
 R
ATINGS
Outdoor 
Unit
Indoor Unit
Cooling Capacity
dBs
Total BTU/h
Sensible BTU/h
EER¹
kWI²
CE120-5
AR-120-2
114,000
83,000
9.0
12.67
84
(2) CA*F4860*6*
114,000
83,000
9.0
12.67
1  Energy Effi
  ciency Ratio
2  kWI = Compressor + Indoor Blower + Outdoor Fan Watts
Capacities
CE120-5
Condenser Fan / Coil
CE120-5
Nominal Cooling (BTU/h)
114,000
Horsepower - RPM
1-930
EER¹
9.0
Fan Diameter/ # Fan Blades
26/3
Decibels
84
Outdoor Nominal CFM
4,400
Compressor
Face Area (ft²)
29.4
RLA / LRA
17.2 / 118
Rows Deep/ Fins per Inch
1/22
Volts
380-420
Fin Type
Ripple
Condenser Fan Motor
Coil No. of Tubes
40
Horsepower / FLA 
1 / 2
Coil Tube Diameter
⅜”
Volts
380
Electrical Data
Refrigeration System
Voltage-Hz / Phase
380/415-50/3
Liquid Valve Size (“O.D.)
⅝”
Min. Circuit Ampacity²
23.6
Suction Valve Size (“O.D.)
1⅛”
Max. Overcurrent Protection³
40 amps
Valve Type
Sweat
Min / Max Volts
342/456
Refrigerant Charge
32
Power Supply Conduit Size
½” or ¾”
Ship Weight (lbs-[kg])
296 [134]
1  Energy Effi
  ciency Ratio 
2  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
3  May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.