Справочник Пользователя для Hoshizaki KM-1301SAH-E

Скачать
Страница из 59
45
E. Thermistor Check
To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 
3 minutes.
6) Disconnect the white thermistor connector from the control board WHITE K3 connector 
and check the resistance between thermistor leads. Normal reading is within 4.7 to 
6.2 kΩ. If outside the normal reading, replace the thermistor. See "V.B. Important Notes
for Component Replacement." If inside the normal reading, continue to the next step.
7) Replace the thermistor in its correct position. See "V.B. Important Notes for Component
Replacement."
8) Reconnect the white thermistor connector to the control board WHITE K3 connector.
9) Replace the control box cover in its correct position, then turn on the power supply.
10) Move the control switch to the "ICE" position.
11) Once the harvest cycle starts, begin timing the harvest cycle.
12) The harvest timer should terminate and end the harvest cycle within 2 to 3 minutes. If 
the harvest timer does not terminate and end the harvest cycle, the harvest timer is bad 
and the control board should be replaced.
F. Adjustment of Water Regulating Valve (water-cooled model) 
The water regulating valve (also called "water regulator") is factory set, and generally no
adjustment is required. However, when necessary, adjust the water regulator using the 
following procedures.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure 
gauge to the high-side line of the system.
2) Five minutes after a freeze cycle starts, 
confirm that the thermometer reads 104°F 
to 115°F (40°C to 46°C). If it does not, 
use a flat blade screwdriver to rotate the 
adjustment screw on the water-regulating 
valve until the temperature is in the proper 
range (rotate counterclockwise to raise 
the temperature or clockwise to lower the 
temperature). See Fig. 5. Next, check that 
the reference pressure is in the range 
indicated in the Head Pressure table in the 
Performance Data section. If it is not in the 
proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable.
Fig. 5
Adjustment Screw
CCW – Higher
CW – Lower
Top View