Справочник Пользователя для Avocent DSR1010

Скачать
Страница из 138
8
        DSR Switch Installer/User Guide
Additional items needed
One IQ module per target server or serial IQ module per serial device
One UTP patch cable per IQ module (4-pair UTP, up to 50 meters)
UTP patch cable(s) for network connectivity (4-pair UTP, up to 50 meters)
One USB2 or USB2L IQ module per target server for virtual media sessions
(Optional) DSView 3 software
(Optional) V.34, V.90 or V.92-compatible modem and cables
(Optional) power control device(s)
Setting up your network
The DSR switching system uses IP addresses to uniquely identify the switch and the target devices. 
The DSR switch family supports both Dynamic Host Configuration Protocol (DHCP) and static IP 
addressing. Avocent recommends that IP addresses be reserved for each switch and that they 
remain static while the switches are connected to the network. 
For additional information on setting up the DSR switch using the DSView 3 software, and for 
information on how the DSR switch uses TCP/IP, see the DSView 3 Installer/User Guide.
Rack Mounting a DSR Switch
A rack mounting kit is supplied with each DSR switch. You may either place the DSR switch on 
the rack shelf or mount the switch directly into an Electronic Industries Alliance (EIA) 
standard rack.
Most DSR switches may be rack mounted in a 1U configuration. The DSR switch family does not 
support a 0U configuration.
Rack mounting safety considerations
Rack Loading - Overloading or uneven loading of racks may result in shelf or rack failure, 
causing damage to equipment and possible personal injury. Stabilize racks in a permanent 
location before loading begins. Mount components beginning at the bottom of the rack, then 
work to the top. Do not exceed your rack load rating.
Power Considerations - Connect only to the power source specified on the unit. When multiple 
electrical components are installed in a rack, ensure that the total component power ratings do 
not exceed circuit capabilities. Overloaded power sources and extension cords present fire and 
shock hazards.
Elevated Ambient Temperature: If installed in a closed rack assembly, the operating 
temperature of the rack environment may be greater than room ambient. Use care not to exceed 
the rated maximum ambient temperature of the switch.
Reduced Air Flow: Install the equipment in the rack so that the amount of airflow required for 
safe operation of the equipment is not compromised.