Дополнительное Руководство для Spectra Logic spectra t120

Скачать
Страница из 29
19
Library Specifications
Single-Frame Library Weight
These specifications should be referenced to prepare for the storage, movement, 
and installation of the primary library frame.
Single-Frame Library Load Distribution
Load per leveler foot on a fully loaded single-frame library—i.e., 24 tape drives and 
83 loaded TeraPack cases installed—is approximately 380 pounds (172 kg). This 
equals approximately 254 pounds per square inch (18 kg per square cm) on each 
foot.
Using a Weight Distribution Plate
If you would like to install the library on a weight-distributing plate, Spectra Logic 
recommends a steel plate with the minimum dimensions of 1/4 X 36 X 30 inches 
(0.6 X 91.4 X 76.2 cm).
Physical Specifications of Library Cascades
Cascade Dimensions
Reference these specifications to prepare your data center for the size and weight of 
a Spectra T950 library cascade. 
Library Weight 
a
a. All weights are approximate and subject to change at any time.
Plus ... 
a
Base Frame
Each LTO Drive
Each SAIT Drive
Each Loaded TeraPack Case
800 lbs. (363 kg)
10.5 lbs. (4.8 kg)
12.3 lbs. (5.6 kg)
5.1 lbs. (2.3 kg)
Specifications for Multi-Frame Cascades 
a
Two 
Frames
Three 
Frames
Four 
Frames
Five 
Frames
Six 
Frames
Eight 
Frames
Height
79.1 in. 
(200.8 cm) 
79.1 in. 
(200.8 cm) 
79.1 in. 
(200.8 cm) 
79.1 in. 
(200.8 cm) 
79.1 in. 
(200.8 cm)
79.1 in. 
(200.8 cm)
Width
59.65 in. 
(151.5 cm) 
88.65 in. 
(225.1 cm) 
117.65 in. 
(298.8 cm) 
146.65 in. 
(372.5 cm) 
175.65 in. 
(446.1 cm)
233.65 in. 
(593.4 cm)