Справочник Пользователя для Eaton PW306BA0U244
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
SPECIFICATIONS
VPC2864-1
VPC2864-A1
VPC3106-C1-15
VPC3106-C2-15
VPC3106-F3-15
VPC2864-4104
Approvals
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
Voltage Input (50/60Hz)
120/208V~
120/208V~
120/208V~
120/208V~
120/208V~
208V~ Delta
Output
208V~
120V~
120V~
120V~
208V~
208V~
Current Rating
Per Phase
16A
Per Phase
16A
Per Phase
24A
Per Phase
24A
Per Phase
24A
Per Phase
24A
Per Phase
Full Load VA
Per Phase
1920VA
Per Phase
1920VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
2880VA
Per Phase
Outlets
(42) IEC C13
(30) 5-15R
(24) 5-15R
(24) 5-20R
(36) IEC C13
(36) IEC C13
Circuit Breaker
NO
NO
(3) 15/15A
(3) 20/20A
(3) 15/15A
(3) 15/15A
Current Monitoring
YES
YES
NO
NO
NO
YES
Power Input Cord/Length
12/5, 6’
12/5, 9’
10/5, 15’
10/5, 15’
10/5, 15’
10/5, 10’
Power Input Connector
L21-20P
L21-20P
L21-30P
L21-30P
L21-30P
L15-30
Mounting Brackets
Included
Tool-less Mounting
RACK MOUNTED
•
70” vertical PDU
(66 inches without mounting brackets)
(66 inches without mounting brackets)
•
Width is 2” and depth is 1.89”
•
Rugged steel construction powder coat black
•
Shipping weight is 16-25 lbs.
CURRENT MONITORING (Optional)
•
2 digit current monitor displays system
current draw to aid in proper system loading
current draw to aid in proper system loading
•
Three position selector switch for selecting
phase A, phase B, or Phase C current draw
•
Current monitor is not available on the
VPC3106 series
VPC3106 series
BRANCH CIRCUIT PROTECTION
•
UL 489 Listed electromagnetic breakers, with
a long time delay curve, provide both manual
on/off switching and open (trip) automatically
with an overload condition
POWER INPUT
•
16 amp models use 12/5 type SOOW cable
•
24 amp models use 10/5 type SOOW cable
•
NEMA style twist lock plugs are attached
OUTLETS
•
VPC2864-1 has (42) IEC 60320 type
C13 receptacles, (14) per section
C13 receptacles, (14) per section
•
VPC2864-A1 has (30) NEMA 5-15R
receptacles, (10) per phase section
receptacles, (10) per phase section
•
VPC3106-C1-15 has (24) NEMA 5-15R
receptacles, (8) per phase section
receptacles, (8) per phase section
•
VPC3106-C2-15 has (24) NEMA 5-20R
receptacles, (8) per phase section
receptacles, (8) per phase section
•
VPC3106-F3-15 has (36) IEC 60320 type
C13 receptacles, (12) per section
C13 receptacles, (12) per section
•
VPC2864-4104 has (36) IEC 60320 type
C13 receptacles, (12) per section
C13 receptacles, (12) per section
MOUNTING BRACKETS
•
All units accept the VPC2864-4104 feature
standard mounting brackets
SUB-HRDWARE-017 (Page 53)
standard mounting brackets
SUB-HRDWARE-017 (Page 53)
•
The VPC2864-4104 features a tool less
mounting. Standard mounting brackets can
be purchased separately.
VPC2864-1
VPC3106-C1-15
VPC2864-4104
VPC2864-A1
VPC2864-4104
Tool-less Mounting