HE120 BY-PASS DRUM HUMIDIFIER
17
69-1860EF—01
5.
Unscrew Back Cover of the Humidistat and remove. 
See Fig. 39.
Fig. 39. Removing Humidistat Back Cover.
6.
Snap two Screw Terminals over the blade terminals on 
the Control Assembly. See Fig. 40
Fig. 40. Installing Screw Terminals.
7.
Connect the two low voltage control wires to the Screw 
Terminals on the Control Assembly. See Fig. 41.
Fig. 41. Wiring Humidistat.
8.
Tuck excess wire into the recessed area on the back of 
the Base Plate.
9.
Use four #6 x 1 in. Sheet Metal Screws to secure the 
assembly to the duct through the mounting holes. 
See Fig. 42.
Fig. 42. Securing Humidistat to Duct.
10.
Push the Setpoint Dial knob onto the control shaft.
Wall Mounting:
IMPORTANT
Mount the control in an area with average room tem-
perature and relative humidity.
1.
Locate the control about 5 ft. above the floor on an 
inside wall. See Fig. 43.
Fig. 43. Selecting Humidistat location.
2.
Drill a 3/8 in. hole in the wall
3.
Run 18-gauge two-strand thermostat wire to the loca-
tion and pull about 6 in. of wire through the hole.
M12841A
CONTROL 
ASSEMBLY
SETPOINT 
DIAL
GASKET
DUCT
60
10
SHEET METAL
SCREWS (4)
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M19925