Cabling the Power Filter Units   
▀  Power Considerations 
 
 
▄  ASR 5000 Installation Guide 
146 
   
Power Considerations 
Each chassis supports one or two 165-amp PFUs.  
The following table describes the power requirements for the chassis. 
Table 46. 
Chassis Power Requirements 
Characteristic
 
Value
 
Input Voltage 
Maximum range: -40VDC to -60VDC 
Nominal range: -48VDC to -60 VDC 
TUV Rated Peak Current Load 
165A @ -48 VDC 
Maximum Peak Power Load 
5760W 
Empty Chassis Maximum Power Load (includes fan trays)  800W 
Line Card (rear-installed) Maximum Power Load 
SPIO: 15W 
FLC2: 13.5W 
GLC2: 10.5W 
RCC: 20W 
QGLC: 15W 
XGLC: 25W 
OLC2: 23W 
CLC2: 23W 
Application Card (front-installed) Maximum Power Load 
SMC: 130W 
PSC: 250W 
PSC2: 325W 
PSC3: 330W 
PPC: 275W 
 
Estimating Power Requirements 
Use the following formula to estimate the total power consumption for each deployed chassis: 
(Total Application Card Maximum Power Load) + (Total Line Card Maximum Power Load) + (Chassis Maximum 
Power Load) 
The calculation for estimating the power required for an ASR 5000 installation with 3 PSCs, 2 SMCs, 2 SPIOs, 2 RCCs, 
and 4 Ethernet 1000 line cards is as follows: 
(250W x 3) + (130W x 2) + ((20W x 2) + (13.5W x 4)) + 800W = 1934W