  Applying Power and Verifying the Installation 
Verifying the Installation  ▀   
 
ASR 5000 Installation Guide  ▄  
 
   
163 
SMC Service LED States 
The Service LEDs on the SMCs indicate that the system requires maintenance or service. Examples are that the system 
could not locate a a valid software image at boot-up, or that a high temperature condition exists. 
This LED is off during normal operation. 
The possible states for this LED are described in the following table. Use the troubleshooting information in the table to 
diagnose the problem. 
Table 54. 
SMC Service LED States 
Color
 
Description
 
Troubleshooting
 
Yellow  System requires maintenance (fan filter, temperature 
warning, PFU outage etc.) 
Refer to the appropriate section of this guide for 
troubleshooting information. 
None 
Card is not receiving power 
No maintenance needed. 
 
SMC Busy LED States 
The Busy LEDs on the SMCs indicate that there is activity on one of their memory devices:  
 
CompactFlash module 
 
PCMCIA device  
 
Nand Flash (used to store SMC firmware) 
 
Hard drive 
The possible states for this LED are described in the following table. If the LED is not green, use the troubleshooting 
information in the table to diagnose the problem. 
Table 55. 
SMC Busy LED States 
Color
 
Description
 
Troubleshooting
 
Green/ 
Blinking Green 
Data is being read from or 
written to one of the memory 
devices. 
No maintenance needed. 
NOTE: If you are removing an SMC from the chassis, it is 
recommended that you wait until this LED is off to ensure the integrity 
of all data being transferred to or from the memory device. 
None 
The memory devices are not in 
use. 
No maintenance needed.