Руководство По Установке для Cisco Cisco Packet Data Gateway (PDG)

Скачать
Страница из 317
ASR 5000 Hardware Platform Overview   
▀  Power Filter Units 
 
 
▄  ASR 5000 Installation Guide 
26 
   
Power Filter Units 
Located at the bottom rear of the chassis are slots for two 165-amp Power Filter Unit (PFU) assemblies. Each PFU 
provides DC power from the site’s power distribution frame (PDF) to the chassis and its associated cards. Each load-
sharing PFU operates independently of the other to ensure maximum power feed redundancy. The maximum input 
operating voltage range of the PFU is -40 VDC to -60 VDC; the nominal range is -48 VDC to -60 VDC. 
Important:
  The ASR 5000 does not offer an AC power supply option. If only AC power is available at the 
installation site, an adequately sized AC-to-DC converter will be required to supply -48 VDC power to the chassis. 
The following drawing shows the PFU and its connectors. 
Figure 6. 
PFU Components 
 
Table 5. 
Power Filter Unit Component Descriptions 
Item
 
Description
 
1
 
Plastic terminal cover
 
2
 
VDC (-48 VDC input terminals)
 
3
 
RTN (voltage return terminals)
 
4
 
PFU handle
 
5
 
Circuit breaker (On/Off) rated at 165A
 
6
 
Power LED