Руководство По Установке для Cisco Cisco ONS 15454 SDH Multiservice Provisioning Platform (MSPP)

Скачать
Страница из 10
5
Installing ONS 15454 SDH TCC-I Cards
78-14610-01
TCC-I Timing Communication and Control Card Description
.
TCC-I Card Specifications
CTC Software
Interface: 10 Base-T LAN (via back plane) 
Access: on the MIC-A/P unit 
Synchronization
Stratum 3 E, per ITU-T G.813
Free running access: accuracy + 4.6 ppm
Holdover Stability: 3.7 * 10
-7
 /day including temperature (<255 slips in first 24 hours)
Reference: External BITS, line, internal
Environmental
Operating Temperature: -5 to +45 degrees Celsius
Operating Humidity: 5 - 95%, non-condensing
Power Consumption: 9.82 W, 0.20 A (AMPS) @ -48V, 33.5 BTU/Hr.
Dimensions
Height: 321.3 mm, (12.650 in.)
Width: 18.2 mm, (0.716 in.)
Depth: 228.6 mm, (9.000 in.)
Depth with backplane connector: 235 mm, (9.250 in.)
Weight not including clam shell: 0.7 kg (1.5 lbs.) 
Compliance
ONS15454 SDH cards, when installed in a system, comply with these standards:
Safety: IEC 60950, EN 60950, UL 60950, CSA C22.2 No. 60950, TS 001, AS/NZS 3260
Table 2
TCC-I System-Level Indicators 
System-Level LEDs
Definition
Red CRIT LED
Used to indicate critical alarms in the network at the local terminal.
Red MAJ LED
Used to indicate major alarms in the network at the local terminal.
Yellow MIN LED
Used to indicate a minor alarm in the network at the local terminal.
Red  REM  LED
Provides first-level alarm isolation. The REM LED turns red when an alarm 
is present in one or several of the remote terminals.
Green SYNC LED
Used to indicate that node timing is synchronized to an external reference.
Green ACO LED
After pressing the alarm cutoff (ACO) button, the green ACO LED 
illuminates. The ACO button opens the audible closure on the backplane. 
ACO state is stopped if a new alarm occurs. After the originating alarm is 
extinguished, the ACO LED and audible alarm control are reset.