Table 8.2.2-1
Item
Setting values
URL
http://<Maintenance IP Address>:<http port#> or
https://<Maintenance IP Address>:<https port#>
This depends on the system configuration.
http port#:Default(8081)
https port#:Default(432)
Username
Account username
Password
Account password
(3) Enter Maintenance Mode.
”.
(4) Confirm the mounting locations of the PSUs. See table 8.2.2-2.
(5) Remove FAN units at the mounting locations of PSUs.
See Appendix C.11, “FANU
”.
Do not remove more than a FAN unit at the same time.
(7) Install the power cable to the main unit. See Table 8.2.2-2.
Table8.2.2-2
Unit type
Power Supply configuration
Refer to
"Input Power Systems"
Cisco C880
200V
standard configuration
200V
redundant power supply configuration
200V
dual power feed configuration
(8) Turn on AC power of the added PSUs.
(9) Navigation Bar [System] → Click on Sub Menu [System Setup].
→
The window shown in “System Setup” appears.
(10) Change the appropriate radio buttons under [Power Feed Mode] and [PSU Redundant Mode].
See Appendix B.7, “Redundant Power Supply and Dual Power Feed Configuration
”.
(11) Change Maintenance Mode disabled. See Appendix B.1.2,” Disabling maintenance mode
”.
41