  Table 8.2.2-1 
Item 
Setting values 
URL 
http://<Maintenance IP Address>:<http port#> or   
https://<Maintenance IP Address>:<https port#> 
 
This depends on the system configuration. 
http port#:Default(8081) 
https port#:Default(432) 
Username 
Account username 
Password 
Account password 
 
(3) Enter Maintenance Mode.   
See Appendix B.1.1, "Enabling maintenance Mode 
(4) Confirm the mounting locations of the PSUs. See table 8.2.2-2. 
(5) Remove FAN units at the mounting locations of PSUs. 
See Appendix C.11, “FANU 
 
Do not remove more than a FAN unit at the same time.   
 
(6) Mount the PSU. See Appendix C.8 PSU 
. 
(7) Install the power cable to the main unit. See Table 8.2.2-2. 
Table8.2.2-2 
Unit type 
Power Supply configuration 
Refer to   
"Input Power Systems" 
Cisco C880 
200V   
standard configuration 
200V   
redundant power supply configuration 
200V   
dual power feed configuration 
 
(8) Turn on AC power of the added PSUs.     
(9) Navigation Bar [System]  →  Click on Sub Menu [System Setup]. 
  The window shown in “System Setup” appears. 
 
(10) Change the appropriate radio buttons under [Power Feed Mode] and [PSU Redundant Mode]. 
     See Appendix B.7, “Redundant Power Supply and Dual Power Feed Configuration   
(11) Change Maintenance Mode disabled. See Appendix B.1.2,” Disabling maintenance mode   
 
 
 
 
 