Power Cabling   
▀  Power Cable Requirements 
 
 
▄  ASR 5500 Installation Guide 
100 
   
Power Cable Requirements 
Sizing Power Cables 
The following guidelines should be adhered to when sizing cable gauges for connecting the PFUs to a rack-mounted 
power distribution panel. 
 
Each conductor between the PDF and PDP should be calculated assuming a 0.3 volt drop from the PDF to the 
panel. 
 
Each cable between the PDP and ASR 5500 PFUs should be calculated a 0.3 volt drop from the panel to the 
chassis. This is a total voltage drop of 0.6 volts. 
 
Use high-flex, multiple-strand cable (minimum 4 AWG) between the power distribution panel and the chassis. 
Important:
  Even if the ASR 5500 chassis will not be completely filled with cards, size the cables for maximum 
power draw according to the above recommendations. This practice facilitates future expansion as more cards are added 
and the power supply is appropriately incremented. 
Terminating Power Cables 
Each cable should be terminated with a 90 degree, 2-hole lug (supplied). Each feed consists of a supply (-48VDC) and 
return (RTN) cable. The feed cables terminate at the rear of each PFU on 0.25-inch posts spaced 0.63-inch on center. 
Cable Routing 
All feed cables must be routed through the openings at the upper rear sides of the chassis. 
Method of Connection 
The method of connection at each PFU terminal is: flat washer, lug, lock washer and nut (7/16-inch). The nut(s) must be 
torqued to 50 in-lb. (5.65 N-m). 
Insulate Lugs 
Use heat shrink tubing or non-conductive tape to insulate much of the exposed metal on the lug without interfering with 
the attachment point. 
Crimp Lugs on Cables 
Use the Panduit® lugs supplied with the chassis (LCD4-14AF-L). The lug must be crimped to the end of a ground cable 
using Panduit crimp tool part number CT-720-1 (die color: gray, P29). The wire strip length is 7/8-inch (22 mm), 
Follow the OEM recommendations for preparing and crimping the lugs on the ends of each feed cable.