Руководство По Установке для Cisco Cisco Packet Data Gateway (PDG)

Скачать
Страница из 195
Chassis Installation   
▀  Grounding the Chassis 
 
 
▄  ASR 5500 Installation Guide 
58 
   
Figure 10.  Location of Chassis Ground Terminals 
 
1
 
Chassis ground point
 
2
 
Grounding cable
 
3
 
2-hole lug
 
4
 
Flat washer
 
5
 
7/16-inch Kep nut
 
 
Grounding Procedure 
Step 1 
Remove the rear bottom cover from the chassis. Grasp both sides of the cover and pull out and up to unsnap the cover. 
Step 2 
Locate the ground terminal on the lower-left corner at the rear of the chassis. 
Step 3 
Use a 7/16-inch nut driver or socket wrench to remove the Kep nuts and washers from each post. 
Step 4 
Insert the lug connected to the grounding cable over the two posts. 
Step 5 
Secure the lug to the ground terminals with the Kep nuts and washers you removed in step 2. The nuts should be 
torqued to 50 in-lb (5.65 N-m).