  Troubleshooting 
Detecting Faulty Hardware  ▀   
 
ASR 5500 System Administration Guide, StarOS Release 16  ▄  
 
   
183 
Figure 11.  DPC/UDPC Status LEDs 
 
The possible states for all of the DPC/UDPC LEDs are described in the sections that follow. 
DPC/UDPC Run/Fail LED States 
The DPC/UDPC Run/Fail LED indicates the overall status of the card. This LED should be green for normal operation. 
The possible states for this LED are described in the following table. If the LED is not green, use the troubleshooting 
information in the table to diagnose the problem. 
Table 21. 
DPC/UDPC Run/Fail LED States 
Color
 
Description
 
Troubleshooting
 
Green
 
Card powered up with no 
errors detected.
 
None needed.
 
Blinking 
Green
 
Card is initializing and/or 
loading software.
 
This is normal operation during boot-up.
 
Red
 
Card powered up with 
error(s) detected.
 
Errors were detected during the Power On Self Tests (POSTs). It is likely that the 
errors were logged to the system's command line interface during boot.
 
None
 
Card is not receiving 
power.
 
Verify that the LEDs on the PFUs are blue. If they are not, refer to 
for troubleshooting information.
 
Verify that the power source is supplying ample voltage and current to the chassis.
 
Verify that the card is properly installed and licensed per the instructions in the ASR 
5500 Installation Guide
.
 
If all of the above suggestions have been verified, it is possible that the DPC/UDPC 
is not functional. Please contact your service representative.