Unpacking and Installing the Cisco ONS 15216 Five-Component Bay Assembly (15216-TERM-BAY)
78-15972-01
  GMT-TPA Fuse and Alarm Panel
Figure 15
110-Type Block Tie-Downs for Existing Alarm Circuitry
Ground and Power
The ground studs and power input and output terminals are mounted on the rear side of the FAP. The 
plastic protective covers install over the input and output power terminals. The covers prevent accidental 
contact with the terminals when power is present in the panel.
Warning
Shut off the power from the power source or turn off the breakers before beginning work.
Warning
This equipment is intended to be grounded. Ensure that the rack is connected to common office earth 
ground during normal use.
Warning
Do not mix conductors of dissimilar metals in a terminal or splicing connector where physical contact 
occurs (such as copper and aluminum, or copper and copper-clad aluminum), unless the device is 
suited for the purpose and conditions of use. 
Warning
Connect the ONS 15216 only to a DC power source that complies with the safety extra-low voltage 
(SELV) requirements in IEC 60950-based safety standards.
Warning
The ONS 15216 relies on the protective devices in the building installation to protect against short 
circuit, overcurrent, and grounding faults. Ensure that the protective devices are properly rated to 
protect the system, and that they comply with national and local codes. 
Warning
A readily accessible fuse must be incorporated in the fixed wiring.
white zone
cable #1
110C-4
110C-4
110C-4
110C-4
110C-4
110C-5
cable #2
cable #3
cable #4
cable #5
cable #6
red zone
black zone
yellow zone
violet zone
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
24 AWG CMP (UL)VERIFIED
110992