Справочник Пользователя для IBM UPS 6000VA LCD 53956KX

Модели
53956KX
Скачать
Страница из 20
IBM 6000VA LCD 4U Rack UPS
3
Features
The IBM 6000VA LCD 4U Rack UPS has the following features and capabilities:
Occupies only 4U of vertical rack space.
Has over 95% energy efficiency at 100% load.
Offers six or 10 output receptacles:
Model 5395-6AX (200V/208V) has two NEMA L6-30R and four IEC 320 C19 receptacles. 
Model 5395-6KX (230V) has four IEC 320 C19 and six IEC 320 C13 receptacles.
Bundled intelligent IBM UPS Manager software enhances control and manageability.
Supports IPv6 for future-proofing IP addressing and security.  
Includes a real-time clock that enables precise shutdown and power up of systems in preferred 
sequence, and time stamping on event logs to track and record specific power-related occurrences. 
Integrates with IBM Systems Director Active Energy Manager for power and thermal trending analysis 
and management.
Has load segments that allow for individual control of receptacle groups, maximizing run time for 
critical devices. 
Supports an optional network management card (part number 46M4140) for enhanced UPS 
monitoring and control.
Allows dual channel communication through the USB port and optional Network Management Card at 
the same time, which is an effective redundancy feature that maximizes communications flexibility. 
Supports an optional Extended Battery Module (EBM) for increased runtime requirements.
Includes a Remote Emergency Power Off (REPO) port to remotely power off the UPS unit to prevent 
battery operation during a power failure.
Requires the following input power:
Single-phase circuit with a 2-pole circuit breaker 
200/208V model: Requires a 40A circuit
230V model: Requires a 32A (Europe) or 40A (North America) circuit
Includes hot swap batteries for maximum uptime, availability, and ease of maintenance.
Supports an optional Environmental Monitoring Probe (part number 46M4113) for thermal 
management requirements (temperature and humidity), which requires that the Network Management 
Card be installed.
Offers an Advanced Battery Management (ABM) three-stage charging technology significantly 
extends battery service life and optimizes recharge time. The three stages are:
The battery is quickly charged to 90% to make sure the UPS is prepared for the next outage.
1.
ABM finishes charging the battery with a more moderate float charge.
2.
After the battery is charged ABM turns the charger off, thereby preventing the batteries from being 
3.
overcharged.