15-6        Using POINT™ I/O Modules on a DeviceNet Network
POINT I/O Adapter 1734-ADN and 1734-ADNX
POINTBlock I/O Module 1734D
Adapter
Status
DeviceNet
Status
PointBus
Status
1734-ADN
DeviceNet
Power
System
Power
1. To change the address, press the button above or below a number.
2. Connect the adapter to the network.
3. Turn on power to the adapter.
4. Check the DeviceNet Status light.
If:
Then the:
green (flashing or solid) address is OK
solid red
address and/or baud rate conflict with another device
off
device is waiting to set its baud rate
When autobaud is on, the device waits until it hears another device 
on the network. It then sets its baud rate to that of the other device.
1. Set the address using the switches on the front of the module.
2. Connect or disconnect and reconnect the module to the DeviceNet network.
3. Check the Network Status light.
If:
Then the:
green (flashing or solid) address is OK
solid red
address and/or baud rate conflict with another device
off
device is waiting to set its baud rate
When autobaud is on, the device waits until it hears another device on the 
network. It then sets its baud rate to that of the other device.