Battery
Nominal DC voltage (intermediate circuit) 120 Vdc
DC window 102 Vdc – 160 Vdc ±1%
Trickle charge voltage
DC window 102 Vdc – 160 Vdc ±1%
Trickle charge voltage
137 Vdc ±1%
Battery charging current (max.) 3.5 Adc per UPS module
Communication
Interfaces RS232
(Sub-D9)
RS485 (Sub-D9 / RJ45)
Additionally: Communication slot
for optional expansion cards (e.g.
AS/400 / SNMP, etc.)
Additionally: Communication slot
for optional expansion cards (e.g.
AS/400 / SNMP, etc.)
Shutdown software on CD
"CompuWatch" for all common
operating systems, e.g. Windows,
Linux, Mac, Unix, FreeBSD,
Novell, Sun
operating systems, e.g. Windows,
Linux, Mac, Unix, FreeBSD,
Novell, Sun
General data
Classification
VFI SS 111 acc. to IEC 62040–3
double-conversion technology
double-conversion technology
Total efficiency AC-AC
PROTECT 1.M (system)
PROTECT 1.M (system)
> 88%
PROTECT 1.040 (module)
> 89%
Inherent noise (1m distance)
PROTECT 1.M (system)
< 62 dB(A)
PROTECT 1.040 (module)
< 55 dB(A)
Cooling type
Forced air cooling through
variable-speed fans
variable-speed fans
Operating temperature range 0 °C to +40 °C
Battery systems
(recommended):
+15°C to +25°C
(recommended):
+15°C to +25°C
Storage temperature range
0°C to +40°C
Relative humidity
20% – 90%