5
Commissioning
5.1
Mechanical Set-Up
Note  the  following  points  when  setting  up  the  UPS  system 
and its external battery units (special accessories):
The  contact  surface  must  be  smooth  and  level.  It  must 
also  be  sufficiently  strong  and  sturdy  to  avoid  vibration 
and shock loads.
Make  sure  the  mounting  is  able  to  support  the  weight: 
This  is  particularly  important  in  conjunction  with  external 
battery units (special accessories).
Set  up  the  units  so  that  adequate  air  circulation  is 
assured. There must be at least 100 mm clearance at the 
back  for  ventilation  purposes.  Do  not  block  the  intake 
openings  on  the  front  and,  if  present,  on  the  side  of  the 
unit. There must be a gap of at least 50 mm here.
Set  up  external  battery  units  (special  accessories)  to  the 
side  of the UPS system. To ensure the greatest  possible 
mechanical  stability,  you  should  not  set  up  the  external 
battery unit(s) above or below the UPS system.
Avoid extreme temperatures! We  recommend  an  ambient 
temperature  of  15  °C  to  25  °C  in  order  to  maximise  the 
service  life  of  the  batteries.  Do  not  expose  the  units  to 
direct  sunlight  or  operate  them  close  to  other  heat 
sources such as radiators.
Protect  the  units  against  external  effects  (in  particular 
moisture and dust). In this regard, please also refer to the 
instructions  in  chapter  4.2,  page  20  in  these  operating 
instructions.
If you transport the unit from a cold room into a warm one, or 
if  the  room  temperature  suddenly  drops  then  condensation 
may  form  inside  the  unit.  To  avoid  any  damage  due  to 
condensation, leave the unit to acclimatise for 2 hours before 
you switch it on.