6.2
Fault Diagnosis / Fault Rectification
The  PROTECT  C.  generates  detailed  error  messages. 
Support personal can localise and interpret faults quickly and 
precisely. 
6.2.1
Error Messages
Problem
Cause
Solution
UPS does not start.
No indication, no audible 
signal even though system 
is connected to mains 
power supply.
Mains and battery voltage 
not in the tolerance range, 
possible battery deep 
discharge.
Check building wiring 
socket outlet and input 
cable.
LED “Line” flashes and 
audible signal sounding 
every 3 minutes.
Phase and neutral 
conductor at input of UPS 
system are reversed.
Rotate mains power 
socket by 180° or 
connect UPS system.
LED “Line” flashes and
LED “Battery” lights up.
Input power and/or 
frequency are out of 
tolerance.
Check input power 
source (Voltage, 
frequency) and inform 
house electrician if 
necessary.
LED “Line” and LED 
“Bypass” light up even 
though the power supply
is available. No supply of 
connected loads.
Inverter not switched on.
Press On-Switch “ON” 
for about 2 seconds.
LED “Inverter” and LED 
“Battery” lights up, and 
audible signal sounding 
every 4 seconds.
Mains power supply has 
failed. Automatic switch
to battery mode. 
Try to replace mains 
supply (possibly 
triggered fuse in sub 
distribution). When 
audible alarm sounding 
every second, battery 
is almost unloaded. At 
this point it is time to 
proceed with an system 
shutdown of all you IT 
equipment.
LED “fault” lights, audible
signal once a second.
Overload of the UPS 
system.
Reduce utilizations of 
UPS by removing loads 
of UPS output.