3. Address Setting
When determining indoor unit addresses with wiring completed without piping construction
(Manual setting by remote controller)
<Address setting procedure>
• Connect a remote controller to the indoor unit whose
address you want to set one to one.
• Turn ON the power.
1
Push 
TEST
 , 
SET
 , and 
CL
 on the remote controller
simultaneously for 4 seconds or more.
2
Set code 
 
  with 
TEMP.
 buttons.
3
Set a refrigerant line address with 
TIME
buttons.
4
Push 
SET
 Indication on the LCD shows normal
operation.
5
Set code 
!
  with 
TEMP.
 buttons.
6
Set indoor unit addresses with 
TIME
 but-
tons.
7
Push 
SET
 Indication on the LCD shows normal
operation.
8
Set code 
"
  with 
TEMP.
 buttons.
9
Set indoor unit addresses with 
TIME
 buttons
as follows:
Individual= 
0000
 , header unit= 
0001
 , follower
unit= 
0002
10
Push 
SET
 Indication on the LCD shows
normal operation.
11
Push 
TEST
 .
Indoor unit address setting is completed.
The operation mode returns to normal OFF.
For systems like this example, connect 
a wired remote controller independently 
without connecting remote controller wires, 
and then set these addresses.
O/U
I/U
O/U
I/U
I/U
I/U
I/U
1
2
2
1
3
2
2
1
2
2
2
2
Wiring example of 2 refrigerant systems
(Solid line: wiring, broken line: refrigerant piping)
(Power cable only)
(Power cable only)
Refrigerant line
address
Indoor unit address
Group address
   1
   1
   1
END
Operation procedure
1
 → 
2
 → 
3
 → 
4
 → 
5
 → 
6
 → 
7
8
 → 
9
 → 
10
 → 
11
  END
Group address
 Individual: 
0000
 
Header unit: 0001
 
Follower unit: 0002
in case of group control
ON / OFF
SET
TEST
FILTER
RESET
CL
VE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
No.
MODE
AN
SET DATA
SETTING
8, 5, 2
11
1
4,
7,
10
3, 6, 9
Refrigerant
line address →
Indoor unit
address →
Group
address →
FILE NO. SVM-12004
– 
86
 –