9.1.5 Environment 
Classes 
of EMC performance 
Hinsichtlich des EMV-Verhaltens gibt es drei allgemeine Klassen, wie nachstehend 
spezifiziert: 
Environment: General Industrial 
Compliance with the EMC Product Standard for Power Drive Systems EN 61800-3 
for use in Second Environment (Industrial) and Restricted Distribution
Table 9-1 
Environment - General Industrial 
EMC Phenomenon 
Standard 
Level 
Emissions: 
 
 
Radiated Emissions 
EN 55011 
Level A1 
Conducted Emissions 
EN 61800-3 
European Amendment EN61800-3-A13 
 
 
 
Immunity: 
 
 
Electrostatic Discharge 
EN 61000-4-2 
8 kV air discharge 
Burst Interference 
EN 61000-4-4 
2 kV power cables, 1 kV control 
Radio Frequency Electromagnetic Field IEC 1000-4-3 
26-1000 MHz, 10 V/m 
Environment: Filtered Industrial 
This level of performance will allow the manufacturer/assembler to self-certify their 
apparatus for compliance with the EMC directive for the industrial environment as 
regards the EMC performance characteristics of the power drive system. 
Performance limits are as specified in the Generic Industrial Emissions and 
Immunity standards EN 50081-2 and EN 50082-2. 
Table 9-2 
Environment - Filtered Industrial 
EMC Phenomenon 
Standard 
Level 
Emissions: 
 
 
Radiated Emissions 
EN 55011 
Level A1 
Conducted Emissions 
EN 55011 
Level A1 
 
 
 
Immunity: 
 
 
Supply Voltage Distortion 
IEC 1000-2-4 
(1993) 
 
Voltage Fluctuations, Dips, Unbalance, 
Frequency Variations 
IEC 1000-2-1 
 
Magnetic Fields 
EN 61000-4-8 
50 Hz, 30 A/m 
Electrostatic Discharge 
EN 61000-4-2 
8 kV air discharge 
Burst Interference 
EN 61000-4-4 
2 kV power cables, 2 kV control 
Radio Frequency Electromagnetic 
Field, amplitude modulated 
ENV 50 140 
80-1000 MHz, 10 V/m, 80% AM, power 
and signal lines 
Radio-frequency Electromagnetic Field,
pulse modulated 
ENV 50 204 
900 MHz, 10 V/m 50% duty cycle, 200 Hz 
repetition rate