2  Installation 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
37
 
2.5.3 
Control Cable Connections 
1.  Feed the control cables into the inverter via one of the gland holes at the I/O 
module end of the terminal housing. 
2.  Run the control cable underneath the I/O board toward the control terminals. 
3.  Connect the control wires in accordance with the terminal information given in 
Figure 2-11. 
4.  Use screened cable for all control wiring. 
8      9
1      2       3      4      5      6        7
 
Terminal Inputs  Parameter 
Default 
operation 
DIN 1 
P0701 = ‘1’ 
ON/OFF1 
DIN 2 
P0702 = ‘12’ 
Reverse 
DIN 3 
P0703 = ‘9’ 
Fault Acknowledge 
6/7 
AIN (-/+) 
P0756 = 0 
0 – 10 V Analogue Input 
 
Option: DIN 4 
P0704 
 0 
 
8/9 
Output Relay 
P0731 = ’52.3’ 
Fault identification 
Figure 2-11  Control Terminals 
 
NOTE 
If a PTC resistor is fitted, this 
should be connected between 4 
(+24 V) and 3 (DIN 3).