6  Troubleshooting 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
82 
6SE6400-5CA00-0BP0  
 
Shock load outside specified limits 
Diagnose & Remedy  
Check the following: 
 
Supply voltage (P0210) must lie within limits indicated on rating plate 
 
Supply must not be susceptible to temporary failures or voltage reductions 
 
Enable kinetic buffering (P1240 = 2) 
F0004  Inverter Over Temperature 
OFF2 
Possible Causes 
 
Ventilation inadequate 
 
Ambient temperature is too high 
Diagnose & Remedy  
Check the following: 
 
Load conditions and duty cycle must be appropriate 
 
Fan must turn when inverter is running 
 
Pulse frequency (P1800) must be set to default value 
 
Ambient temperature could be higher than specified for the inverter 
Additional meaning for MM440 Frame size FX & GX: 
Fault value  = 1:  Rectifier overtemperature 
 
 = 2:  Ambient overtemperature 
 
 = 3:  EBOX overtemperature 
F0005 Inverter 
I
2
t OFF2 
Possible Causes 
 
Inverter overloaded 
 
Duty cycle too demanding 
 
Motor power (P0307) exceeds inverter power capability (r0206) 
Diagnose & Remedy  
Check the following: 
 
Load duty cycle must lie within specified limits 
 
Motor power (P0307) must match inverter power (r0206) 
F0011 Motor 
Over 
Temperature 
OFF1 
Possible Causes 
Motor overloaded 
Diagnose & Remedy  
Check the following: 
 
Load duty cycle must be correct 
 
Motor nominal overtemperatures (P0626-P0628) must be correct 
 
Motor temperature warning level (P0604) must match 
If P0601 = 0 or 1, check the following: 
 
Check if name plate data are correct (if not perform quick commissioning) 
 
Accurate equivalent circuit data can be found by performing motor identification (P1910=1) 
 
Check if motor weight (P0344) is reasonable. Change if necessary 
 
Via P0626, P0627, P0628 the standard overtemperatures can be changed, if the motor is not a 
Siemens standard motor 
If P0601 = 2, check the following: 
 
Check if temperature shown in r0035 is reasonable 
 
Check if the sensor is a KTY84 (other sensors are not supported) 
F0012  Inverter temp. signal lost  
OFF2 
Possible Causes 
Wire breakage of inverter temperature (heatsink) sensor 
F0015  Motor temperature signal lost 
OFF2 
Possible Causes 
Open or short circuit of motor temperature sensor. If signal loss is detected, temperature monitoring 
switches over to monitoring with the motor thermal model