6  Troubleshooting 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
91
 
DAC parameters should not be set to identical values, since this would produce illogical results. 
Fault value  = 0:  Parameter settings for output identical 
 
1:  Parameter settings for input identical 
 
2:  Parameter settings for output do not correspond to DAC type 
A0922  No load applied to inverter 
Possible Causes 
No Load is applied to the inverter. 
As a result, some functions may not work as under normal load conditions. 
A0923  Both JOG Left and JOG Right are requested 
Possible Causes 
Both JOG right and JOG left (P1055/P1056) have been requested. This freezes the RFG output 
frequency at its current value. 
A0936  PID Autotuning Active 
Possible Causes 
PID Autotuning (P2350) selected or running 
A0952  Belt Failure Warning 
Possible Causes 
Load conditions on motor indicate belt failure or mechanical fault. 
Diagnose & Remedy  
Check the following: 
 
No breakage, seizure or obstruction of drive train. 
 
If using an external speed sensor, check for correct function. Check parameters:  
P2192 (delay time for permitted deviation) 
 
If using the torque envelope, check parameters:  
P2182 (threshold frequency f1) 
P2183 (threshold frequency f2) 
P2184 (threshold frequency f3) 
P2185 (upper torque threshold 1) 
P2186 (lower torque threshold 1) 
P2187 (upper torque threshold 2) 
P2188 (lower torque threshold 2) 
P2189 (upper torque threshold 3) 
P2190 (lower torque threshold 3) 
P2192 (delay time for permitted deviation)