Allen-Bradley Drive Fault Codes
Table 56 (continued)
Allen-Bradley Drive Fault Codes
Fault
Description
Corrective Action/
Remarks
02
Motor Temp
Fault
Fault
The motor thermal switch path is
open.
open.
Motor temperature high. Check for: ambient air, cooling
fan blockage or operation, break in switch wire path (not
on all machines).
fan blockage or operation, break in switch wire path (not
on all machines).
03
Power Loss Fault
DC Bus voltage remains below
85% nominal for longer than .5
seconds.
85% nominal for longer than .5
seconds.
Monitor incoming AC line for low voltage or line power
interruption.
interruption.
04
Under Voltage Fault
DC Bus voltage fell below
minimum.
minimum.
Monitor AC incoming AC line for low voltage or line
power interruption.
power interruption.
05
Over Voltage Fault
DC Bus maximum voltage
exceeded.
exceeded.
Monitor the AC line for high line voltage or transient
conditions. High voltage can result from motor
regeneration. Buck transformer may be required.
conditions. High voltage can result from motor
regeneration. Buck transformer may be required.
06
Motor Stall
Motor has stalled. Motor load is
excessive.
excessive.
Check motor wiring and connection terminals. Check wash
basket freedom of movement and excess belt tension.
basket freedom of movement and excess belt tension.
07
Motor Overload Fault
Internal electronic overload trip.
Excessive motor load exists.
Excessive motor load exists.
Check motor wiring and connection terminals. Check wash
basket freedom of movement and excess belt tension.
basket freedom of movement and excess belt tension.
08
Over Temperature Fault
Excessive heat detected by
heatsink transducer.
heatsink transducer.
Clear blocked or dirty heatsink fins. Check ambient
temperature. Check for blocked or nonoperating fan.
temperature. Check for blocked or nonoperating fan.
10
Serial Fault
Drive lost communication with
controlling device.
controlling device.
HIM removed while power applied, cycle power to clear.
12
Overcurrent Fault
Overcurrent detected in
instantaneous hardware trip circuit.
instantaneous hardware trip circuit.
Check short circuit at the controller output or excessive
load conditions at motor.
load conditions at motor.
22
Controller Reset Fault
Stop input not present.
Check stop input into control terminal board. Close door
and ensure any jumpers are placed correctly.
and ensure any jumpers are placed correctly.
32
EEPROM Fault
EEProm has invalid data.
Consult the factory for further instructions.
33
Max Retries Fault
Controller failed to reset fault
within the number of retries.
within the number of retries.
Fault exists that must be corrected before further operation.
Check “Fault Buffer 1” on 1305 and 1336 for specific fault
that triggered max retries fault.
Check “Fault Buffer 1” on 1305 and 1336 for specific fault
that triggered max retries fault.
38
Phase U Fault
Phase-to-ground fault detected
between controller and motor in
Phase U.
between controller and motor in
Phase U.
Check wiring between the drive and motor. Check for
grounded phase.
grounded phase.