PowerFlex 40 and 400 Drive Control Logic
33
F232120
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Allen-Bradley Drive Fault Codes
Table 20 (continued)
Allen-Bradley Drive Fault Codes
Fault
Description
Corrective Action/
Remarks
003
Power Loss Fault
DC Bus voltage remains below 
85% nominal for longer than .5 
seconds.
Monitor incoming AC line for low voltage or line power 
interruption.
004
Under Voltage Fault
DC Bus voltage fell below 
minimum.
Monitor AC incoming AC line for low voltage or line 
power interruption.
005
Over Voltage Fault
DC Bus maximum voltage 
exceeded.
Monitor the AC line for high line voltage or transient 
conditions. High voltage can result from motor 
regeneration. Buck transformer may be required.
006
Motor Stall
Motor has stalled. Motor load is 
excessive.
Check motor wiring and connection terminals. Check wash 
basket freedom of movement and excess belt tension.
007
Motor Overload Fault
Internal electronic overload trip. 
Excessive motor load exists.
Check motor wiring and connection terminals. Check wash 
basket freedom of movement and excess belt tension.
008
Over Temperature Fault
Excessive heat detected by 
heatsink transducer.
Clear blocked or dirty heatsink fins. Check ambient 
temperature. Check for blocked or nonoperating fan.
012
Overcurrent Fault
Overcurrent detected in 
instantaneous hardware trip circuit.
Check short circuit at the controller output or excessive 
load conditions at motor.
024
Unable to Decelerate
DC Bus regulation prevents 
machine from decelerating 
typically due to high input voltage, 
motor regeneration or unstable 
motor operation.
Verify DC Bus (d005) is less than 340V for 200-240V 
applications or 680V for 380-480V applications. Check for 
an imbalanced wash load. Check for proper speed 
increment through all extract speeds.
033
Max Retries Fault
Controller failed to reset fault 
within the number of retries.
Fault exists that must be corrected before further operation. 
Check “Fault Buffer 1” on 1305 and 1336 for specific fault 
that triggered max retries fault.
038
Phase U Fault
Phase-to-ground fault detected 
between controller and motor in 
Phase U.
Check wiring between the drive and motor. Check for 
grounded phase.