Planning Information
Model I 363418 (R) Pro Island Hood
Dimensions in parentheses are in
millimeters unless otherwise specified.
5
I N S T A L L A T I O N N O T E S
Refer to the illustrations and specifications
for overall dimensions and installation specifics.
Wolf Pro island hoods are recommended for
use with any Wolf cooking appliance. The hood
must overlap the cooking surface by a minimum
of 3" (76) on either side.
Installation of all Pro island hoods should be
30" (762) to 36" (914) from the bottom of the
hood to the countertop. Follow the dimensions
shown in the Installation illustration.
Wolf Pro island hoods are shipped without a
blower assembly. Internal, in-line and remote
blower assemblies are available. Blower options
also vary with the volume of air that needs to
be moved and the length of the duct run. Refer
to the charts at the end of this section for Pro
ventilation recommendations and blower
options.
IMPORTANT NOTE: Install this ventilation hood
only with a Wolf blower.
Pro island hoods require a separate,
grounded 110/120 V AC, 60 Hz power supply.
The service should have its own 15 amp circuit
breaker. Placement of the electrical supply is
not critical, as long as you provide a minimum
of 6" (152) of 120 V AC, 60 Hz power cable.
Location of electrical is centered through the
top of the hood as shown in the Installation
illustration on page 4.
You must follow all National Electrical Code
regulations. In addition, be aware of local codes
and ordinances when installing your service.
Refer to the installation instructions shipped
with each Wolf product for detailed specifica-
tions. This information can also be found on
our website, wolfappliance.com.