6.0 Electrical Wiring Instructions
IMPORTANT NOTICE: The electrical wiring of this spa must meet 
the requirements of the National Electrical Code/USA (NEC) and any 
applicable state or local codes. The electrical circuit must be installed 
by a qualified electrician and approved by a local building/electrical 
inspection authority.
1.  Convertible 120/240V Denali/Tacoma Models Only:
• 
120V “Plug-in” Operation: This spa must operate on the supplied  
 
120V GFCI cord at its original length or must be hard-wired for 
 
longer runs. Never use an extension cord for any reason! 
• 
Convertible 120/240V Heater Operation: The included 120V GFCI 
 
cord must be discarded for 240V heater operation. This spa must  
 
be hard-wired. Supplying power to either configuration above which  
 
is not in accordance with these instructions will void both the 
 
independent testing agency listing and the manufacturer’s warranty.
2.   Dedicated 230-240V Burlington Models: 
 
This spa must be permanently connected (hard-wired) to the power  
 
supply. No plug-in connections or extension cords are to be  
 
used in conjunction with the operation of this spa. Supplying  
 
power to the spa which is not in accordance with these instructions  
 
will void both the independent testing agency listing and the 
 
manufacturer’s warranty.
3.  The power supplied to this spa must be a dedicated circuit with no  
 
other appliances or lights sharing the power provided by the circuit.
4.  To determine the current, voltage and wire size required, refer to 
 
section 5.0 “Power Requirements” (page 9-10).
•   Wire size must be appropriate per NEC and/or local codes.
•   We recommend type THHN wire.
• 
All wiring must be copper to ensure proper connections. Do not  
 
use aluminum wire.
•   When using wire larger than #6 (10mm
2
), add a junction box near  
 
the spa and reduce to short lengths of #8 (8.4mm
2
) wire to connect  
 
to the spa.
5.  The electrical supply for this product must include a suitably rated  
 
switch or circuit breaker to open all ungrounded supply conductors  
 
to comply with section 422-20 of the National Electrical Code/USA,