OPERATION
AC OPERATION
OVERLOAD INDICATOR
(RED)
OUTPUT INDICATOR
(GREEN)
PLUG
Start the engine (see page
and make sure the output
indicator (green) comes on.
Turn on the appliance.
Determine if the cause is a short circuit in a connected appliance or an
overload. Correct the problem and restart the generator.
Before connecting an appliance to the generator, make sure that the
appliance is in good working order and that its electrical rating does
not exceed that of the receptacle.
Plug an appliance into the
appropriate receptacle.
Most motorized appliances require more than their electrical rating for
startup. When an electric motor is started, the overload indicator (red)
may come on. This is normal if the overload indicator (red) goes off
within 9 seconds. If the overload indicator (red) stays on, consult your
generator dealer.
If the generator is overloaded (see page
), or if there is a short circuit
in a connected appliance, the overload indicator (red) will come on. If
the overload indicator (red) stays on continuously for more than 4
seconds, current to the connected appliance(s) will shut off, and the
output indicator (green) will go off. Stop the engine and investigate
the problem.