QuickMedia™ Receiver/Processor                             Crestron QM-RMCRX 
for each of the three outputs channels. These values are only settable using DMT 
software. 
When <RecallFilterPreset> goes high and remains high, the current filter 
values stored in <FilterPreset#> (as set in the DMT software) will be recalled 
and applied to the outputs. Valid values for <FilterPreset#> range from 1 to 6. 
If <RecallFilterPreset> goes high and <FilterPreset#> is set to an invalid 
value (out of the 1 to 6 range) all filters will be cleared, and all signals will pass 
unaffected. This is the same as recalling a filter preset in which every filter is set 
to 0. 
Slot 10: C2I-RMC-FRONTPANEL 
The C2I-RMC-FRONTPANEL is the non-programmable front panel of the QM-
RMCRX and other 2-Series control systems. It does not provide an LCD display 
or push buttons. 
Compiling and Uploading a Program to the 
Control System 
After you have completed your SIMPL Windows program for the QM-RMCRX, 
you must compile and upload the program to the control system.  
To compile the program, simply click the Convert/Compile button 
 on the 
SIMPL Windows toolbar, or select Project | Convert/Compile (you can also 
press F12). A status bar indicates the progress of the compile operation. After 
the operation is complete, a window displays information about the program 
such as the number and type of signals, and memory usage. 
The compiled program is stored as an SPZ file in the same directory as the 
source file. There are a number of ways to upload an SPZ file to the control 
system. 
1.  Immediately after compiling the program you have the option to 
transfer the file to the control system. 
2. Alternatively, 
click 
the 
Transfer button 
 on the SIMPL Windows 
toolbar, or open Viewport and click File Transfer | Send Program
3. Click 
Browse, locate the SPZ file and click Open. This displays the 
program's header information and enables one or both of the What to 
Send
 check boxes. If the program does not contain any SIMPL+ 
modules, only the SIMPL Program check box is enabled. If it does 
contain SIMPL+ modules, then the SIMPL+ Program(s) check box is 
also enabled. Select one or both check boxes and then click Send 
Program 
to begin the transfer. 
NOTE:  Unlike X-Generation processors, the 2-Series processor does not 
require a separate step to create a permanent memory image. Also, the 2-Series 
adds the ability to automatically retrieve the current program from the control 
system. Simply verify that the Retrieve Current Program Before Overwriting 
check box is selected. 
You can also click Report Program Information or F7 from Diagnostics in 
Viewport
 to display the header information of the currently loaded program. 
Program information is also displayed in the Viewport console whenever power 
is removed and re-applied to the QM-RMCRX. 
48 
 QuickMedia™ Receiver/Processor: QM-RMCRX 
Operations Guide - DOC. 6236A