HEATING AND COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (L/s) x
TEMP. DIFF. (DEG. C) x
FLUID FACTOR* =
(kW)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE
=
 
(DEG C)
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE
=
 
(DEG C)
*Use 500 for water, 485 for antifreeze.
DESCRIPTION
HEATING
COOLING
NOTES
Voltage
Compressor Amp
Suction Temperature
Suction Pressure
2a Saturation Temperature
2b Superheat
Discharge Temperature
Discharge Pressure
4a Saturation Temperature
4b Subcooling
Liquid Line Temperature
Source Water In Temperature
Source Water Out Temperature
Temperature Difference —
Source Water In Pressure
Source Water Out Pressure
9a Pressure Drop
9b Flow Rate (L/s)
10 Load Water In Temperature
11 Load Water Out Temperature
Temperature Difference —
12 Load Water In Pressure
13 Load Water Out Pressure
13a Pressure Drop
13b Flow Rate (gpm)
COMPRESSOR
DISCHARGE
SUCTION
HWG*
EXPANSION
VALVE
FILTER
DRIER
REVERSING
VALVE
HEATING POSITION
COOLING POSITION
1
COAX
CO
A
X
5
12
10
13
11
9
7
8
6
4
3
2
FP2:
HEATING
LIQUID
LINE
5
FP1:
COOLING
LIQUID
LINE
CONDENSER (HT G)
EVAPORAT OR (CLG)
CONDENSER (COOLING)
EVAPORATOR (HEATING)
WATER-TO-WATER UNITS
REFRIG FLOW - HEATING
REFRIG FLOW - COOLING
Source
Load
LEGEND
*Turn off HWG (hot water generator)
before troubleshooting.
CLG
— Cooling
HTG
— Heating
a50-8465