The calibration data is stored in a U32 array, though each Offset field 
should be interpreted as a signed value.
The NI 9219 returns calibrated 24-bit (padded to 32-bits) AI data for all 
modes and ranges.
To convert raw data into engineering units use the following formula: 
y = m*x + b
b = offset based on range of the device (such as, –60 for ± 60 Volts 
Voltage Measurement Range)
m = Gain (Full-Range/ (2
24
)): (such as, 120/(2
24
) for ± 60 Volts Voltage 
Measurement Range)
14
3-Wire RTD
Pt1000
15
Pt100
16
Quarter-Bridge
350 
Ω
17
120 
Ω
18
Half-Bridge
 ±500 mV/V
19
Reserved
20
Full-Bridge
±62.5 mV/V
21
±7.8 mV/V
Table 35.  NI 9219 Calibration Data