NI 9472/9474
Ferrules ............................................. 0.25 mm
2
 to 2.5 mm
2
Weight
NI 9472/9474 with
screw terminal ............................ 150 g (5.3 oz)
NI 9472 with DSUB ................... 145 g (5.1 oz)
Safety
NI 9472/9474 with Screw Terminal Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM .............................. 30 VDC max
Isolation
Channel-to-channel .................... None
Channel-to-earth ground
Continuous ........................... 250 V
rms
Measurement Category II
Withstand ............................. 2,300 V
rms
, verified by a 5 s 
dielectric withstand test 
Measurement Category II is for measurements performed on 
circuits directly connected to the electrical distribution system.