Caution
For Zone 2 applications, install a protection 
device between the V
sup
 and COM terminals on the 
NI 9472/9474. The device must prevent the input 
V
sup
-to-COM voltage from exceeding 42 V if there is a 
transient overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment 
under DEMKO Certificate No. 03 ATEX 0324020X. Each module 
is marked 
 II 3G and is suitable for use in Zone 2 hazardous 
locations. If you are using the NI 9472/9474 in Gas Group IIC 
hazardous locations or in ambient temperatures of 
–40 °C
≤ Ta ≤ 70 °C, you must use the device in an NI chassis that 
has been evaluated as EEx nC IIC T4, Ex nA IIC T4, or 
Ex nL IIC T4 equipment.