Unitary Products Group
COMPRESSORS
Units are shipped with compressor mounting factory-adjusted
for shipping. 
Loosen compressor mounting bolts a half turn 
before operating unit.
TABLE 3: NATURAL GAS APPLICATION DATA
AVAILABLE ON MODELS
INPUT CAPACITY
(MBH)
1
OUTPUT 
CAPACITY
(MBH)
GAS RATE
2
FT.
3
/HR.
NUMBER OF
BURNERS
TEMP. RISE °F AT FULL 
INPUT
3
MIN.
MAX.
1-1/2, 2, 2-1/2 3 TON
45
36
42
2
25
55
2 & 2-1/2 TON
70
56
65
3
30
60
3 TON
70
56
65
3
25
55
3-1/2 TON, 4 & 5 TON
80
64
74
3
25
55
3 TON
90
72
84
4
30
60
3-1/2 TON
108
87
100
4
45
75
4 & 5 TON
108
87
43
4
30
60
4 & 5 TON
135
108
126
5
35
65
1.
Heating capacity valid for elevations up to 2000 feet above sea level.  For elevations above 2,000 feet, rated capacity should be reduced by 4% for 
each 1,000 feet above sea level.
2.
Based on 1075 BTU/Ft.
3
.
3.
The air flow must be adjusted to obtain a temperature rise within the range shown.  Continuous return air temperature should not be below 55°F.