Appendix D
Advanced Function Block Behavior
©
 National Instruments Corporation
D-3
To prevent windup, the control loop needs to be aware when it is unable to 
control the process. If the downstream block can no longer control the 
process, it reports a status of Bad to the upstream block. This breaks the 
cascade until automatic control can be resumed, in which case cascade 
initialization takes place again.
Remote Cascades
If a host application (rather than another block) provides the setpoint of a 
block, FOUNDATION Fieldbus provides the 
Remote Cascade
 mode. The 
remote cascade mode is equivalent to 
Cascade
 mode, except that the 
cascade input parameter is 
RCAS_IN
 instead of 
CAS_IN
, and the back 
calculation output is 
RCAS_OUT
 instead of 
BKCAL_OUT
. Unlike 
CAS_IN
 and 
BKCAL_OUT
, which are input/output parameters, 
RCAS_IN
 and 
RCAS_OUT
 
are contained parameters and can only be written by a host application. To 
allow the controlled block to enter 
Remote Cascade
 mode, the host 
application must act as the upstream block in the cascade initialization and 
implement the status handling described above.
Figure D-2.  Remote Cascade Model
There is a second remote mode in which a cascade must be initialized: 
Remote Output (
ROut
 mode). Unlike 
RCas
 mode, where the block setpoint 
is set remotely, in 
ROut
 mode the block output is set by the host application. 
The back calculation output for 
ROut
 mode is 
ROUT_OUT
, and the cascade 
input is 
ROUT_IN
. Otherwise, cascade initialization proceeds normally.
RCAS_OUT
Downstream
RCAS_IN
Host
Application