Chapter 3
Example Applications
©
 National Instruments Corporation
3-9
You can avoid setting the 
XD_SCALE
 value manually if you set the 
CFG_OPTS
 option called Automatically adjust XD_SCALE. This 
allows the FP-3000 to copy the value from 
FP_TC_120_RANGE
 
straight into the 
XD_SCALE
 parameter.
2.
Determine the output scale. If you want to output the temperature in 
degrees Kelvin, you can set 
OUT_SCALE
 to the same values as 
XD_SCALE
 above. If you want to change to Celsius, you can do so by 
setting 
OUT_SCALE
 as follows:
OUT_SCALE
EU at 100%
1775.00
EU at 0%
-273.15
Units Index °C
Decimal
2
3.
Tell the block to use the scaling parameters. The block is flexible 
enough to either ignore scaling (
Direct
), use linear scaling 
(
Indirect
), or use square root scaling (
Indirect square root
). 
Since you want the block to use linear scaling, set the 
L_TYPE
 
parameter of the block to 
Indirect
.
Set Up Scheduling
Before the block will operate, you need to schedule the block to execute. 
All Fieldbus function blocks (including function blocks on the FP-3000) 
execute according to a schedule. You can specify the order of function 
blocks in the schedule and the rate at which the schedule is repeated. To 
make the configurator create a schedule for your block, follow these steps:
1.
Double-click on Function Block Application in the tree view of the 
configurator.
2.
Drag the block from the tree view to the application view. The 
configurator automatically generates a schedule for the block that 
causes it to run every second (refer to the documentation that came 
with your configurator for information about changing the execution 
period). 
3.
To download this schedule to the device, select Configure»Download 
Configuration
. A dialog box appears that enables the configuration to 
be downloaded. Go through the download process, as described in the 
documentation that came with your configurator. Since the block is not 
scheduled when you start the download, its actual mode does not 
change until the download is complete.