Chapter 3
Example Applications
©
 National Instruments Corporation
3-17
Figure 3-6.  PID Alarm Connection Dialog Box
5.
Download the configuration. The PID now detects a high limit alarm 
whenever the temperature exceeds 40° C, and the alarm is transmitted 
to the interface on your PC. You need a separate program (such as the 
Lookout HMI package from National Instruments) to receive, display, 
and acknowledge the alarms. You can verify that the alarms are being 
detected by the PID block by reading the 
HI_ALM
 parameter. The 
Alarm State changes, and the Alarm Timestamp is set when the alarm 
goes active.