Chapter 4
Block Reference
4-4
©
 National Instruments Corporation
LOG (FieldPoint Log Block) (FP-3000 Specific)
The LOG block contains a log of error conditions and events detected by 
the device as it operates.
STAT (FieldPoint Statistics Block) (FP-3000 Specific)
The STAT block contains a set of parameters that can be used to examine 
how the device is performing. It contains statistics describing the 
performance of local function blocks and the network interface.
Function Blocks and FieldPoint Modules
The FP-3000 supports a wide variety of I/O channels, each with different 
types of configuration information. For example, a thermocouple channel 
includes parameters for thermocouple type and has ranges for different 
temperatures; a current loop channel includes parameters for filter 
frequency and has a different group of available ranges to chose from. 
Because of these differences in parameters, the FP-3000 has a block 
specific to each type of channel it supports. To use a thermocouple 
connected to an I/O channel on an FP-TC-120 module, the FP-3000 
provides a FP-TC-120 AI Block. This block is a standard Analog Input 
block augmented with parameters specific to the thermocouple channel on 
the FP-TC-120.
Binary Open/Close 
(
BINARY_OP/BINARY_CL
)
BINARY_OP
 only functions when 
ENABLE_OP
 has a value of 
Discrete_State_1
BINARY_CL
 only functions when 
ENABLE_CL
 
has a value of 
Discrete_State_1
. If both 
BINARY_OP
 and 
BINARY_CL
 are set and enabled, neither one takes effect.
Operator Command 
(
OP_CMD_CXO
)
OP_CMD_CXO
 is a contained bit string parameter that has a bit for 
Open and a bit for Close. Open only functions when 
ENABLE_OP
 has 
a value of 
Discrete_State_1
. Close only functions when 
ENABLE_CL
 has a value of 
Discrete_State_1
. If both Open and 
Close are set and enabled, neither one takes effect.
Table 4-1.  CDO Block Interlock Priorities (Continued)
Input 
(Descending Priority)
Notes