Справочник Пользователя для National Instruments FP-3000

Скачать
Страница из 118
Appendix B
Troubleshooting
©
 National Instruments Corporation
B-3
I/O Module Problems
FP-3000 offers diagnostic capabilities to help find problems with the 
I/O modules you have plugged in.
Software Configuration Problems
The FP-3000 software consists of a number of function blocks that you can 
instantiate, or create, from a host configuration utility. Each function block 
represents an input channel, an output channel, or some control behavior. 
In addition, the FP-3000 contains a Resource Block which allows you to 
configure some overall behavior for the FP-3000. All of these blocks 
contain parameters, which are values that you can set to configure things 
like channel ranges, scaling to engineering units, and failsafe behavior.
Some problems are generic to all blocks, and some problems occur only 
with certain types of blocks. Table B-3 lists problems that can occur in 
many types of blocks. Table B-4 lists problems that can occur only in the 
resource block.
Table B-2.  I/O Module Problems
Problem
Solutions
The green READY LED does 
not light when the module is 
plugged  in.
Make sure the module is firmly seated. Also, make sure the 
terminal base is firmly attached to the terminal base on its left. 
Look for bent pins on the bottom of the module.
The red LED is lit on an I/O 
channel.
TC module: The thermocouple is not connected or is 
broken.
AI module: The input wires are not connected or are 
broken.
AO module: The module cannot source as much current 
as the FP-3000 is requesting. This might be because the 
output wires are not connected or broken, or there could 
be some other electrical problem.