Appendix C
Fieldbus Parameters
C-4
©
 National Instruments Corporation
BLOCK_RESET
Lets you reset the statistics or the configuration of an individual function 
block.
BYPASS
Allows the normal control algorithm to be bypassed if the 
CONTROL_OPT
 
parameter’s 
Bypass Enable
 option is selected. If control is bypassed, the 
PID uses its setpoint value as its output value and does not attempt to do 
any PID control.
CHANNEL
Used by I/O function blocks to select a physical I/O channel. This mapping 
is defined by the manufacturer. In the FP-3000, this parameter is 
automatically updated when the 
FIELDPOINT_MODULE
 and 
FIELDPOINT_CHANNEL
 parameters are modified.
CHECKBACK
A list describing the state of the interlock logic in the CDO block. Use 
CHECKBACK
 to determine how interlocks are operating.
Device Needs 
Maintenance Now
0x2000
The device needs to be maintained now.
Power-Up
0x4000
The device has just powered up.
Out of Service
0x8000
The block is currently out of service.
Table C-2.  Block Reset Options
Option
Description
Contained Parameters
Sets all the contained parameters (standard and FP-3000 
specific) of the function block to default values. This is useful 
to set a specific block to a known state without affecting the 
behavior of the other blocks in the FP-3000. The block should 
be in OOS mode to reset the contained parameters.
Statistics
Resets the various statistics counts associated with the block. 
Table C-1.  Error Codes (Continued)
Error Code
Code
Description