F300 ELECTRONIC AIR CLEANER
9
68-0240EF-5
Install Turning Vanes
!
Mount turning vanes inside the elbow or angle fitting that is 
directly against the air cleaner cabinet. See Fig. 7.
Fasten Cabinet To Ductwork
!
Install a transition when the opening in the air cleaner 
cabinet and the duct are different sizes. See Fig. 4.
!
Fasten the other side of the cabinet to the elbow using 
sheet metal screws, rivets, or slip joints as appropriate. If 
drilling holes, use locking pliers to help hold the unit in place 
during drilling. See Fig. 7.
Fig. 7. Connect ductwork to air cleaner. (Note turning 
vanes. Locking pliers hold duct to air cleaner cabinet 
during installation.)
Seal Joints
!
Seal all joints in the return air system between the air 
cleaner and the furnace to prevent dust from entering the 
clean airstream. Use optional air cleaner cabinet gasket kit 
(part no. 32002109-001), mastic or foil tape.
Position Cell Key
The electronic cell must always be installed so the ionizer 
section is on the upstream side. A factory-installed cell key on 
the bottom of the cabinet allows the cell to be inserted in only 
one direction. If the arrow molded into the plastic key points in 
the same direction as the airflow, the ionizer is always on the 
upstream side.
If position of the key must be reversed, proceed as follows:
1. Remove the electronic cell.
2. Remove the screw holding the cell key in place. See Fig. 8.
Fig. 8. Position of cell key determines orientation of cell 
(arrow on key must point downstream).
3. Turn the key around and place it over the opposite holes. 
The tab on the bottom fits into the larger hole, and the 
screw fits into the smaller hole. Make sure the arrow on 
the key points in the direction of the air flow (down-
stream).
4. Tighten the screw into the new hole.
5. Insert the electronic cell. The ionizer section will now be 
on the air-entering (upstream) side of the cabinet.
Attach Cell Handles
Cell handles included with the air cleaner must be installed on 
the end of the cell closest to the access door. To install:
1. Orient the cell as it will be when installed. The gray 
contact board must be up and the airflow arrow stamped 
into the cell must point downstream.
2. Hold the handle sideways and insert the solid tab on the 
back of the handle into the slot in the cell. Turn the 
handle 90 degrees clockwise to align the divided tab with 
the square hole. See Fig. 9.
Fig. 9. Install the handle on the end of the cell closest to 
the access door.
3. Insert the divided tab into the square hole.
4. Fold up the wedge and insert it into the divided tab to 
lock the handle in place. If necessary, press with a blunt 
instrument like the end of a pliers.
M20815
LOCKING
PLIERS
TURNING
VANES
PREFILTER GUIDES
CELL KEY
M5639
CELL 
KEY
ALTERNATE
HOLES FOR
KEY
CELL KEY
SCREW
DOWNSTREAM
AIRFLOW
M6047A
ROTATE 90
DEGREES
FOLD TAB
TO LOCK 
HANDLE
IN PLACE
INSTALL HANDLE ON END OF CELL 
CLOSEST TO ACCESS DOOR