Справочник Пользователя для Honeywell easy-to-see t841a

Скачать
Страница из 4
69-1043-2   G.H.   Rev. 3-03 
www.honeywell.com/yourhome
HEAT PUMP THERMOSTAT
Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN  55422
Scarborough, Ontario
M1V 4Z9
SETTINGS
Temperature Setting
The enlarged, raised numbers on the right edge of the 
thermostat can be used for easy temperature setting by 
touch or sight while moving the temperature setpoint 
lever to the desired temperature setting. The large 5, 6, 7 
and 8 refer to 50°F (10°C), 60°F (16°C), 70°F (21°C) and 
80°F (27°C), respectively. A click is heard with indents 
every two degrees as the temperature setpoint lever is 
moved. See Fig. 1.
System Switch Setting
The enlarged, raised letters on the left bottom edge of the 
wallplate can be used for easy recognition of System 
switch settings: 
For the T841A Thermostat: The large EH, H, O and C 
refer to EM. HT., HEAT, OFF and COOL. 
For the T841B Thermostat: The large H, O and C refer 
to EM. HT., HEAT, OFF and COOL. 
The System switch settings control the system operation 
as follows:
EM.HT (only on T841A): Emergency heat relay is 
energized. Cooling system is off. Compressor is 
de-energized. Fan runs on call for heat if the Fan 
switch is in the AUTO position. EM. HT. LED is on.
HEAT: Heating system is automatically controlled by 
the thermostat. Cooling system is off.
OFF: Both the heating and cooling systems are off. If 
the fan is set to the AUTO position, the cooling fan 
is also off.
COOL: Cooling system is automatically controlled by 
the thermostat. Heating system is off.
Fan Switch Setting
On theT841A,B, large A, O raised letters on the right 
bottom edge of the wallplate refer to AUTO and ON fan 
settings. The Fan switch settings control the fan as 
follows:
AUTO: Fan operates in response to thermostat in both 
heating and cooling.
ON: Fan operates continuously.
CHECKOUT
Heating
Move the System switch on the thermostat to HEAT and 
the Fan switch to AUTO. Move the temperature setpoint 
lever to about 10°F (6°C) above the room temperature. 
Heating should start and the fan should run. Move the 
setpoint lever about 10°F (6°C) below the room 
temperature. Heating and fan should shut off.
IMPORTANT
To prevent compressor short cycling, a mini-
mum-off timer can be included to prevent the 
compressor from starting for up to five minutes 
from when the thermostat last turned off the 
compressor, or from when the system first 
received power.
Cooling
CAUTION
Compressor Damage Hazard. 
Operating cooling equipment in cold weather 
can damage compressor.
Do not operate air conditioner if outdoor 
temperature is below 50°F (10°C).
Move the System switch on the thermostat to COOL and 
the Fan switch to AUTO. Move the temperature setpoint 
lever about 10°F (6°C) below the room temperature. 
Cooling and fan should start (see Note in Checkout 
section). Move the setpoint lever about 10°F (6°C) above 
the room temperature. Cooling and fan should shut off.
Fan
Move System switch to OFF, and Fan switch to ON. The 
fan should run continuously. Move Fan switch to AUTO. 
In this position, the fan operates in response to the 
thermostat in both heating and cooling.