Справочник Пользователя для Ideal nd2365

Скачать
Страница из 10
8
True RMS AC Current
Range
Resolution
Max
Accuracy
Voltage 
Display Burden 
40mA
10µA
40.00
±(2.0% +5)
200mV max
400mA
0.1mA
400.0
2Vmax
10A
10mA
10.00
±(2.5% +5)
2V max
AC Conversion Type: AC conversions are ac-coupled, true
rms responding, calibrated to the rms value Sine wave input.
Overload Protection: 1A (500V) fast blow fuse for mA input
16A (500V) fast blow fuse for A input
Crest Factor: +1.5% additional error for C.F. from 1.4 to 3
+3.0% additional error for C.F. from 3 to 4
To Measure True RMS AC Current:
1.  Plug the black test lead into the COM port and the red test 
lead into the mA or A port.
2.  Set the rotary switch to the mA or A position.
3.  Push the blue button until 
AC
is shown on the display.
4.  Connect the meter in series with the load or circuit.
5.  Measure AC Current.
7
DC Volts
Range
Resolution
Max Display
Accuracy 
400mV
100µV
400.0
±(0.25% +5)
4V
1mV 4.000 
±(0.4% 
+1)
40V
10mV
40.00 ±(0.25% 
+1)
400V
100mV
400.0
1000V
1V
1000
Input Impedance: 10M
Ω
(over 1000M
Ω
in 400mV range)
To Measure DC Voltage:
1.  Plug the black test lead into the COM port and the red test 
lead into the V
Ω
Hz port.
2.  Set the rotary switch to the V position.
3.  Push the blue button until 
DC
is shown on the display.
4.  Connect the meter in parallel with the load or circuit.
5.  Measure DC Voltage.
Circuit Connection:
Hz
True RMS
Circuit Connection:
Hz